How do I troubleshoot a non working/reading Temperature/ Moisture cable Integris System

This article will walk you through the procedure of troubleshooting a non working/reading temperature/moisture cable on the Integris System provided the RTU is reporting as well as other cables in the bin.


  1. Look for obvious damage to the Sensing Cable, lead wire INT2, RTU, or the RTU Expander . Replace any damaged components that you find, either by purchasing new ones from your OPIsystems Inc. dealer, or contacting your local dealership to arrange a warranty replacement.
  2. Check the cable wiring on the RTU or RTU Expander, this could be located inside an enclosure box on-top of the bin or at the bottom of the bin. Open it up with a Philips head screwdriver and check to see if the wiring is solid with no loose connections or obvious shorts. A multitester (voltmeter) would be of great help determining if there are open wires and/or short circuited wires.). If you have a BLUE RTU with an expander check to see if the cable wiring will be loose in the respective channel that the cable terminates to. If you have the old style (RVS1) RTU, check the cable wiring in the terminal block. If its a single cable system check the wiring to the RTU terminal as well, make sure that there are no obvious wiring mistakes with the terminals.


    1. Check the INT2 or the Moisture Cable with a StorMax monitor if you have one or have access to one.
      Connect a Stormax hand-held monitor at the cable's head(pig tail coming out of the cables' head), if you do not get a meaningful reading then the cable is bad and needs to be replaced by purchasing a new one or contacting your dealership for warranty claims
      image-png-Feb-18-2021-05-05-19-50-PM 

      If the cable reads fine at the head, then try to read the cable from the point where the lead wire terminates inside the cable node and if it does not read, then you have a faulty lead wire, replace the lead wire. 
    2. j,If all the previous steps have been ruled out, then Check for bad channel by moving the temp/moisture cable to a different position, preferably a free position on the cable node connector terminal and unmap and re-map the corresponding cable node on your OPI BLUE account, then
      • check if the cable shows up on the new channel and
        • if it does, then associate this "new" cable to the position of the "missing" cable. 
        • If it doesn't then contact support for further troubleshooting steps possibly a cable replacement will be needed.